Cooling Tower
A Tower cools 875gpm from 95 degreesF to 85 degreesF at 72 degreesF
wet bulb temperature. What is the:
Range = Inlet Temp - Outlet Temp
(ex: Range = 95 - 85 = 10 degreesF)
Approach = Out Temp - Wet Bulb Temp
(ex: Approach = 85 - 73 = 13 degreesF)
Heat Rejection = FlowGpm X RangeDegF X 500
(ex: Heat Rejection = 875 x 10 x 500 = 4,375,000btu/hr = 4,375 MBH)
Typical Drift Loss = .002% X Recirculated Flow Rate
(ex: Typical Drift Loss = .00002 X 875 = .0175Gpm)
Evaporation RateGpm = FlowGpm X RangedegF / 1,000
(ex: Evaporation Rate = 875 X 10 / 1,000 = 8.75gpm)
Bleed RateGpm = Evap. RateGpm / (Cycles-1)
(ex: Bleed Rate3 Cycles = 8.75 / (3-1) = 4.4Gpm)
Make-up Water RequirementGpm = Evaporation RateGpm X [Cycles/(Cycles-1)]
(ex: Make-upat 3 cycles = 8.75Gpm x 3/2 = 13.1Gpm)
EQUALIZER SIZE CHART
Flow to each tower (GPM) |
Equalizer size (in.) |
UP TO 122 |
3 |
123-239 |
4 |
240-627 |
6 |
628-1167 |
8 |
1168-1925 |
10 |
1926-2820 |
12 |
2821-3465 |
14 |
2336-3850 |
(2)10 |
3851-5640 |
(2)12 |
5641-6930 |
(2)14 |
<
|