Evaporative Condenser Formulas:

Total Heat of Rejection (THR):

Open Compressors:
THRBTU/HR = Evaporator CapacityBTU/HR + Compressor BHP X 2545

Hermetic Compressors:

THRBTU/HR = Evaporator CapacityBTU/HR + Compressor KW X 3415


Evaporation RateGPM = THRBTU/HR / 500,000


Bleed RateGPM = Evaporation RateGPM / (Cycles - 1)


Make-upGPM = Evaporation RateGPM X [Cycles / (Cycles - 1)]