Evaporative Condenser Formulas:
Total Heat of Rejection (THR):
Open Compressors:
THRBTU/HR = Evaporator CapacityBTU/HR + Compressor BHP X 2545
Hermetic Compressors:
THRBTU/HR = Evaporator CapacityBTU/HR + Compressor KW X 3415
Evaporation RateGPM = THRBTU/HR / 500,000
Bleed RateGPM = Evaporation RateGPM / (Cycles - 1)
Make-upGPM = Evaporation RateGPM X [Cycles / (Cycles - 1)]